Oil Transformers

Off-Circuit Tap-Changing Oil-Immersed Transformer (S11–S22 series)

Standard oil-immersed distribution transformer with off-circuit tap changing for seasonal voltage adjustment. 10 / 20 / 35 kV.

Key parameters

Rated capacity
50–10000 kVA
Voltage class
35 kV
Tap changing
Off-circuit tap changing ±5% / ±2×5%
Vector group
Yyn0 / Yd11 / YNd11
Request a quote for this product

Overview

The most economical distribution transformer in the range, with a manual off-circuit tap changer (±2×2.5 %) set while de-energised. Robust, efficient and widely deployed for general-purpose medium-voltage distribution.

Technical parameters

35kV class S11 off-circuit tap-changing distribution transformer performance data
ModelRated capacity (kVA)No-load loss (W)Load loss (W)No-load current (%)Impedance (%)Total weight (kg)
S11-5050168115026.5714
S11-10010023219191.86.51110
S11-12512527222611.76.51310
S11-16016028826891.66.51475
S11-20020034431631.56.51707
S11-25025040837621.46.51850
S11-31531548845321.46.52360
S11-40040058454721.36.52442
S11-50050068865841.26.52787
S11-63063083278661.16.52868
S11-800800984940516.53640
S11-1000100011521154316.53900
S11-125012501408139360.96.54680
S11-160016001696166730.86.54835
35kV class S11 (630-10000kVA) off-circuit tap-changing power transformer performance data
ModelRated capacity (kVA)No-load loss (kW)Load loss (kW)No-load current (%)Impedance (%)Total weight (kg)
S11-6306300.8327.8661.16.54095
S11-8008000.9489.40516.54550
S11-100010001.15211.1516.54880
S11-125012501.40813.940.96.55100
S11-160016001.69616.670.86.55280
S11-200020002.17618.380.76.55380
S11-250025002.5619.670.66.56160
S11-315031503.0423.090.5677645
S11-400040003.61627.360.5678905
S11-500050004.3231.380.48710330
S11-630063005.24835.060.48712330
S11-800080007.238.480.427.516150
S11-10000100008.70445.320.427.519920

Request a quote for this product

Replies within 1 business day